MMSU GSD Nberic Mechanical Services
JANSSEN SAGADRACA
OIC-CHIEF, MECHANICAL SERVICES
A/C Technician
-N. NALUPTA
-A. NARDO
-R. BLE
01/03-12/2022
J. SAGADRACA
A. NARDO
J. Garcia
SWIMMING POOL
=>Oversee the operation and cleaning
of the following:
->PUMP 10-11-12
-Clean filter
-Pressure (ok)
->PUMP 1-2-3
-Clean filter
-Pressure (ok)
-Pipeline Problem
->Good Running Condition
01/21/22
J.SAGADRACA
N.NALUPTA
A.ALLEN
R.BLEZA
=>>FOR AIRCON
=>Oversee the repair and maintenance of power spray.
-worn out 15 pcs Oring (Replace new)
-repair electrical wirings
-replace capacitor
-change oil
-Good Running Condition
01/20/2022
J.SAGADRACA
J.GARCIA
SNT GENSET OPERATION
-START = 3:00 PM
-SHUTDOWN = 4:30 PM
-NO. OF RUN HRS = 1.5 HRS
-FUEL CONSUMPTION = 8.038 HRS
-GOOD RUNNING CONDITION
01/20/22
J.SAGADRACA
N.NALUPTA
A.ALLEN
J.GARCIA
J.BLEZA
COLLEGE OF MEDICINE
=>>FOR AIRCON
=>Oversee the general cleaning of 3units3HP Panasonic split
type wall mounted aircon.
->COM LIBRARY ACU1
-Clean (Indoor &Outdoor)
-Good Running Condition
->COM LIBRARY ACU2
-Clean (Indoor &Outdoor)
-Good Running Condition
->COM LIBRARY ACU3
-Clean (Indoor &Outdoor)
-Good Running Condition
NATIONA BIOENERGY RESEARCH AND INNOVATION CENTER
=>>FOR AIRCON
=>Oversee the check up malfunction 3HP Everest split type
ceiling mounted aircon.
->NBERIC-CONFERENCE
-3 mins shutdown compressor
-error 33 code
-On Going
01/17/22
J.SAGADRACA
N.NALUPTA
A.ALLEN
R.BLEAZA
=>>FOR AIRCON
=>Oversee the general cleaning of 2units Panasonic 3HP split
type wall mounted aircon.
->COM-ACU3 BIOCHEMISTRY
-Clean (Indoor & Outdoor)
-Good Running Condition
->COM-ACU4 BIOCHEMISTRY
-Clean (Indoor & Outdoor)
-Good Running Condition
01/17/22
J.SAGADRACA
N.NALUPTA
A.ALLEN
=>>FOR AIRCON
=>Oversee the general cleaning of 3units Panasonic 3HP split
type wall mounted aircon.
->COM-LECTURE ROOM 5
-Clean (Indoor & Outdoor)
-Good Running Condition
->COM-ACU1 MICROLAB
-Clean (Indoor & Outdoor)
-Good Running Condition
->COM-ACU2 MICROLAB
-Clean (Indoor & Outdoor)
-Good Running Condition
01/13-14-17/2022
J.SAGADRACA
A.NARDO
R.BLEZA
NBERIC
=>Oversee the monitoring of "NAWASA GAUGE METER"
-81686 m3
01/14/2022
J.SAGADRACA
J.Garcia
SWIMMING POOL
=>Oversee the operation and cleaning
of the following:
->PUMP 4
-Clean (Filter)
-Presure 18 psi
->PUMP 5
-Clean (Filter)
-Presure 18 psi
-V3 & V4 pipeline leak
->PUMP 6
-Clean (Filter)
-Presure 19 psi
-> Good Running Condition
01/14/22
J.SAGADRACA
N.NALUPTA
A.ALLEN
COM-ADMIN OFFICE
=>>FOR AIRCON
=>Oversee the general cleaning of
Panasonic 2HP split type wall mounted
aircon.
-Clean (Indoor & Outdoor)
-Defection air swing motor
(For replacement air swing motor)
-Good Running Condition
01/13/22
J.SAGADRACA
N.NALUPTA
A.ALLEN
R.BLEZA
CRL- SOIL & WATER LAB
=>>FOR AIRCON
=>Oversee the general cleaning and check
up of 4 units Panasonic 1.0hp window
type aircon.
->ACU 1 Panasonic SN = 930407565
-Clean (Evaporator and Condenser)
-Good Running Condition
->ACU 2 Panasonic SN = 930407169
-Clean (Evaporator and Condenser)
-Good Running Condition
->ACU 3 Panasonic SN = 930407245
-Clean (Evaporator and Condenser)
-Good Running Condition
->ACU 4 Panasonic SN = 862403843
-Clean (Evaporator and Condenser)
-Good Running Condition
01/03-12/2022
J.SAGADRACA
J.Garcia
SWIMMING POOL
=>Oversee the operation and cleaning
of the following:
->PUMP 10-11-12
-Clean filter
-Pressure (ok)
->PUMP 7-8-9
-Clean filter
-Pressure (ok)
->PUMP 4-5-6
-Clean filter
-Pressure (ok)
->PUMP 1-2-3
-Clean filter
-Pressure (ok)
->Good Running Condition
01/10/22
J.SAGADRACA
N.NALUPTA
A.ALLEN
ILLARRDEC OFFICE
=>>FOR AIRCON
=>Oversee the not functioning 2 units
(Panasonic 2HP & Kolin 2HP)window
type aircon.
->Panasonic
-Defection compressor capacitor(Replace new capacitor)
-General cleaning (Evaporator & Condenser)
-Good Running Condition
->Kolin
-Defective compressor (Grounded)
-Defective compressor capacitor
-Recommend for condemned
J.SAGADRACA
A.NARDO
COE
=>>METAL WORKS
->Oversee the cutting of metals
-Done
01/05-07/22
J.SAGADRACA
N.NALUPTA
A.ALLEN
R.BLEZA
ADMI-VPAA
=>FOR AIRCON
->Oversee the weak cooling of 2.5hp
Panasonic split type wall mounted aircon
-add R32 Freon
-Good Running Condition
CRL-CONFERENCE
=>FOR AIRCON
->Oversee the not functioning 3 units 5TR
Carrier split type floor mounted aircon
-Carrier 1 (trip breaker-ok)
-Carrier 2 (trip breaker-ok)
-Carrier 3
-Defective fan motor(Replace new fan motor)
-Defective PCB Board(Replace new PCB Board)
-Defective Breaker (Replace new breaker)
-Good Running Condition
CRL-CLIMATE CHANGE
=>FOR AIRCON
->Oversee the not functioning 2HP Carrier
window type aircon
-Worn out compressor and fan motor
wirings (Replace new wirings)
-Defective fan motor (Replace new fan motor)
-Defective fan capacitor (Replace new fan capacitor)
-General cleaning (Evaporator & Condenser)
-Good Running Condition
01/04/22
J.SAGADRACA
N.NALUPTA
A.ALLEN
R.BLEZA
COE-CHEMICAL FACULTY
=>FOR AIRCON
->Oversee the general cleaning of 2HP LG split
type wall mounted aircon
-clean indoor & outdoor
-Good Running Condition
CHS-PHARMACY
=>FOR AIRCON
->Oversee the malfunction 2HP Carrier window type
aircon
-shutdown in 30 mins
-defective fan motor capacitor
-ONGOING
01/03/2022
J.SAGADRACA
N.NALUPTA
A.ALLEN
ADMI-STRATCOM
=>FOR AIRCON
->Oversee the general cleaning and repair the
noisy parts of 2HP Carrier, window type aircon
-clean condenser and evaporator
-repair air swing
-good running condition
JUNE 2, 2021
Aircon Technician
-J. Sagadraca
-G. Sagadraca
-N. Nalupta
*General cleaning @ CTE ADMIN BLDG (Dean, Cashier, Registrar and Research & Extension)
-4 Units window type
JUNE 7, 2021
Aircon Technician
-J. Sagadraca
-G. Sagadraca
-N. Nalupta
*Defective 35uf capacitor@ PCC-DIRECTOR OFFICE
-1 unit window type
- replacement 35 uf capacitor
June 7, 2021
SWIMMING POOL
-J. SAGADRACA
-J. Garcia
Maintenance
*General cleaning
-filter 1 & 2
-pump filter 1 & 2
JUNE 2, 2021
Aircon Technician
-J. Sagadraca
-G. Sagadraca
-N. Nalupta
*General cleaning @ CHS-PHARMACY RM 210 &211
-1 unit split tyoe wall mounted
*Adjust manual selector@ CHS-PHARMACY RM 211
-1 unit Window Type
June 4, 2021
GENSET
-J. SAGADRACA
-R. BLEZA JR
NO ELECTRICITY
Data Monitoring & Operator and ITC Genset
JUNE 2, 2021
Aircon Technician
-J. Sagadraca
-G. Sagadraca
-N. Nalupta
*General cleaning @ CTE LIB WING ABC
-6 units Window Type
-3 units split type wall mounted
*Defective Capacitor 5uf & 35 uf @ CTE LIB WING AC
-2 units Window Type
JUNE 1, 2021
Aircon Technician
-J. Sagadraca
-G. Sagadraca
-N. Nalupta
*General cleaning 1UNIT ST WM ELP
MAY 31, 2021
GENSET
-J. SAGADRACA
-A. NARDO
NO ELECTRICITY
Data Monitoring & Operator and ITC Genset
MAY 31, 2021
Aircon Technician
-J. Sagadraca
-G. Sagadraca
-N. Nalupta
*Cleaning filfer CAFETERIA
*General cleaning WT 1 unit security & 2units COA
MAY 28, 2021
Aircon Technician
-G. Sagadraca
-N. Nalupta
*additional freon, 2 unit ST WM VPAA and Canteen
MAY 27, 2021
GENSET
-R. Bleza Jr
NO ELECTRICITY
Data Monitoring & Operator and ITC Genset
MAY 26-27, 2021
Aircon Technician
-G. Sagadraca
-N. Nalupta
-R. Bleza Jr
-A. Nardo
*Detach 1 unit split type wall mounted from COE and install to VPAA
MAY 24, 2021
Aircon Technician
-G. Sagadraca
-N. Nalupta
*Detach, 1 unit split type wall mounted due to defective compressor, beyond economical repair. Recommended for condemned VPAA
MAY 24,2021
Aircon Technician
-G. Sagadraca
-N. NALUPTA
*General Cleaning, 2 units Window Type Legal and Administrative.
MAY 24, 2021
Genset Maintenance/Operator/Monitoring
-R. BlezaJr
Change Batery and Charged @ ITC Genset
APRIL 2021
Aircon Technician
-G. Sagadraca
-N. Nalupta
*General Cleaning, 2 unit Split Type Wall Mounted Records
MARCH 2021
Aircon Technician
-N. Nalupta
-G. Sagadraca
*General Cleaning,1 unit Split Type Wall Mounted Cashier
MARCH 2021
Aircon Technician
-G. Sagadraca
-R. Bleza Jr
Installation, 1unit Split Type Wall Mounted
Click here to claim your Sponsored Listing.
Category
Contact the business
Website
Address
Batac
2906
Opening Hours
Monday | 8am - 5pm |
Tuesday | 8am - 5pm |
Wednesday | 8am - 5pm |
Thursday | 8am - 5pm |
Friday | 8am - 5pm |
Brgy. 8 Acosta
Batac, 2906
ADS Engineering Services offers: - Civil/Structural designs - assistance in the preparation of plans
Taft Street
Batac, 2906
Specializes in: ● ELECTRICAL DESIGN (Residential, Commercial & Industrial) ● Supervision of electrical works ● Sign and seal Electrical permit ● Electrical Wiring, Layout, Installa...
Julian Domingo Street Bgry. Caunayan, Batac City, Ilocos Norte
Batac
Engineering Service for your Electrical Plan Design, Electrical Wiring and Solar Installation
Batac, 2906
Design, Consultancy, Sign and Seal Services since 2017: Professional Mechanical Engineer & Master Plumber